Panasonic / Sunx GX-F/H

Excel Automation is an authorized Panasonic / Sunx distributor. Contact us with sales and application support.

Type NPN output PNP output
Model No.
(Note 2)
Front sensing GX-F6A(I) GX-F6B(I) GX-F6A(I)-P GX-F6B(I)-P
Top sensing GX-H6A(I) GX-H6B(I) GX-H6A(I)-P GX-H6B(I)-P
CE marking directive compliance EMC Directive, RoHS Directive
Max. operation distance
(Note 3)
1.6 mm 0.063 in ± 8 %
Stable sensing range
(Note 3)
0 to 1.3 mm 0 to 0.051 in
Standard sensing object Iron sheet 12 x 12 x t 1 mm 0.472 x 0.472 x t 0.039 in
Hysteresis 20 % or less of operation distance
(with standard sensing object)
Repeatability Along sensing axis, perpendicular to sensing axis: 0.04 mm 0.002 in or less
Supply voltage 12 to 24 V DC+10/-15% Ripple P-P 10 % or less
Current consumption 15 mA or less
Output NPN open-collector transistor
– Maximum sink current: 100 mA
– Applied voltage: 30 V DC or less (between output and 0 V)
– Residual voltage: 2 V or less (at 100 mA sink current)
PNP open-collector transistor
– Maximum source current: 100 mA
– Applied voltage: 30 V DC or less(between output and +V)
– Residual voltage: 2 V or less (at 100 mA source current)
Utilization
category
DC-12 or DC-13
Output operation Normally open Normally closed Normally open Normally closed
Max. response frequency 400 Hz
Operation indicator Orange LED
(lights up when the output is ON)
Pollution degree 3 (Industrial environment)
Protection IP68 (IEC), IP68G (Note 4, 5)
Ambient temperature -25 to +70 ℃ -13 to +158 ℉, Storage: -40 to +85 ℃ -40 to +185 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 95 % RH
Voltage withstandability 1,000 V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 500 Hz frequency, 3 mm 0.118 in double amplitude (Max. 20 G) in X, Y and Z directions for two hours each
Shock resistance 10,000 m/s2 acceleration (1,000 G approx.) in X, Y and Z directions three times each
Sensing range
variation
Temperature
characteristics
Over ambient temperature range -25 to +70 ℃ -13 to +158℉: Within ±8 % of sensing range at +23℃ +73 ℉.
Voltage
characteristics
Within ±2 % for +10/-15 % fluctuation of the supply voltage
Material Enclosure: PBT, Indicator part: Polyester
Cable 0.15 mm2 3-core oil, heat and cold resistant cabtyre cable, 1 m 3.281 ft long
Cable extension Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable.