Amerimation LSLV G100

Eagle Sensors & Controls is an authorized Amerimation distributor. Contact us with application and sales support.

Key Features

  • Great Reliability
    • Meets UL 61800-5-1
    • Military (MIL 217Plus) design based methodology
    • Enhanced materials and manuafcturing processes
  • Great Performance
    • Enhanced motor control-sensorless & V/F performance
    • User-friendly-easy tuning sensorless control
    • Suitable for most applications
  • User Friendly
    • Easy to install, use and maintain
    • Various options

① Rated Motor

0004 0.4kW
0008 0.75kW
0015 1.5kW
0022 2.2kW
0040 4.0kW
0055 5.5kW
0075 7.5kW

② Input Voltage

2 3-phase 200~240[V]
4 3-phase 380~480[V]

③ Keypad

E LED Keypad

④ UL Type

O UL Open

 EMC Filter

F Built-in EMC(C2)
N Non-EMC

⑥ Reactor

N Non Reactor

Specifications

3-Phase 200V Class (0.4~7.5kW)
0004 0008 0015 0022 0040 0055 0075
Motor Rating Heavy Duty HP 0.5 1.0 2.0 3.0 5.4 7.5 10
kW 0.4 0.75 1.5 2.2 4.0 5.5 7.5
Normal Duty (ND) HP 1.0 2.0 3.0 5.4 7.5 10 15
KW 0.75 1.5 2.2 4.0 5.5 7.5 11
Output Rating Capacity [kVA] Heavy Duty (HD) 1.0 1.9 3.0 4.2 6.5 9.1 12.2
Normal Duty (ND) 1.2 2.3 3.8 4.6 6.9 11.4 15.2
Rated Current (3-Phase Input) [A] Heavy Duty (HD) 2.5 5.0 8.0 11.0 17.0 24.0 32.0
Normal Duty (ND) 3.1 6.0 9.6 12.0 18.0 30.0 40.0
Rated Current (1-Phase Input) [A] Heavy Duty (HD) 1.5 2.8 4.6 6.1 9.3 12.8 17.4
Normal Duty (ND) 2.0 3.6 5.9 6.7 9.8 16.3 22.0
Frequency [Hz] 0~400Hz (IM sensorless: 0~120Hz)
Voltage [V] 3-Phase 200~240V
Input Rating Voltage [V] 3-Phase 200~240VAC (-15%~+10%)
Frequency [Hz] 50~60Hz (±5%)
Rated Current [A] Heavy Duty (HD) 2.2 4.9 8.4 11.8 18.5 25.8 34.9
Normal Duty (ND) 3.0 6.3 10.8 13.1 19.4 32.7 44.2
Weight [kg] 1.04 1.06 1.36 1.4 1.89 3.08 3.21
3-Phase 400V Class (0.4~7.5kW)
0004 0008 0015 0022 0040 0055 0075
Motor Rating Heavy Duty HP 0.5 1.0 2.0 3.0 5.4 7.5 10
kW 0.4 0.75 1.5 2.2 4.0 5.5 7.5
Normal Duty (ND) HP 1.0 2.0 3.0 5.4 7.5 10 15
KW 0.75 1.5 2.2 4.0 5.5 7.5 11
Output Rating Capacity [kVA] Heavy Duty (HD) 1.0 1.9 3.0 4.2 6.5 9.1 12.2
Normal Duty (ND) 1.5 2.4 3.9 5.3 7.6 12.2 17.5
Rated Current (3-Phase Input) [A] Heavy Duty (HD) 1.3 2.5 4.0 5.5 9.0 12.0 16.0
Normal Duty (ND) 2.0 3.1 5.1 6.9 10.0 16.0 23.0
Rated Current (1-Phase Input) [A] Heavy Duty (HD) 0.7 1.4 2.1 2.8 4.9 6.4 8.7
Normal Duty (ND) 1.3 1.9 2.8 3.6 5.4 8.7 12.6
Frequency [Hz] 0~400Hz (IM sensorless: 0~120Hz)
Voltage [V] 3-Phase 380~480V
Input Rating Voltage [V] 3-Phase 380~480VAC (-15%~+10%)
Frequency [Hz] 50~60Hz (±5%)
Rated Current [A] Heavy Duty (HD) 1.1 2.4 4.2 5.9 9.8 12.9 17.5
Normal Duty (ND) 2.0 3.3 5.5 7.5 10.8 17.5 25.4
Weight [kg] 1.02 (1.04) 1.06 (1.08) 1.4 (1.44) 1.42 (1.46) 1.92 (1.98) 3.08 (3.24) 3.12 (3.28)
Control
Control Method V/F, Slip Compensation, Sensorless Vector
Frequency Setting Resolution Digital command: 0.01Hz Analog command: 0.06Hz(maximum frequency: 60 Hz)
Frequency Accuracy 1% of the maximum output frequency
V/F Pattern Linear, squared, user V/F
Overload Capacity HD: 150% 1 minute, ND: 120% 1minute
Torque Boost Manual/Automatic torque boost
Operation
Operation Mode Select key pad, terminal strip, or communication operation
Frequency Setting Analog: -10~10[V], 0~10[V], 4~20[mA] Digital: Keypad
Operation Function PID control, 3-wire operation, Frequency limit, Second function, Anti-forward and reverse direction rotation, Commercial transition, Speed search, Power braking, Leakage reduction, Up-down operation, DC braking, Frequency jump, Slip compensation, Automatic restart, Automatic tuning, Energy buffering, Flux braking, Fire mode
Input Multi-Function Terminal (5 Points) NPN (Sink) / PNP (Source) Selectable
Function: Forward run, Reverse run, Reset, External trip, Emergency stop, Jog operation, Multi-step frequencyhigh, middle, low, Multi-step acceleration/ deceleration-high, middle, low, DC braking at stop, 2nd motor select, Frequency up/down, 3-wire operation, Change into normal operation during PID operation, Change into main body operation during option operation, Analog command frequency fixing, Acceleration/deceleration stop etc. Selectable
Analog Input V1: -10~10V, I2 4~20mA
Output Multi-function Relay Terminal Fault output and drive operation status output (N.O., N.C.) less than AC 250V 1A, less than DC 30V 1A
Analog Output 0~12Vdc: Frequency, Output current, Output voltage, DC stage voltage etc. selectable
Protective Function
Trip Over current trip, external signal trip, ARM short current fault trip, over heat trip, input imaging trip, ground trip, motor over heat trip, I/O board link trip, no motor trip, parameter writing trip, emergency stop trip, command loss trip, external memory error, CPU watchdog trip, motor light load trip Over voltage trip, temperature sensor trip, inverter over heat, option trip, output image trip, inverter overload trip, fan trip, pre-PID operation failure external brake trip, low voltage trip during operation, low voltage trip, analog input error, motor overload trip, over torque trip, under torque trip
Alarm Command loss trip warning, overload warning, light load warning, inverter overload warning, fan operation warning, braking resistance braking rate warning, rotor time constant tuning error, inverter pre-overheat warning, over torque warning, under torque warning
Momentary Power Loss HD below 15ms (ND below 8ms): Continuous operation (To be within rated input voltage, rated output) HD above 15ms (ND above 8ms): Automatic restart operation enable
Environment
Cooling Type Forced fan cooling structure
Protection Degree IP20/UL Open (Default), UL Enclosed type 1 (Option)
Ambient Temperature Ambient temperature under the condition of no ice or frost. HD: -10~50℃(14~122°F) / ND: -10~40℃(14~104°F) [However, recommended to use load below 80% when using at 50°C under light load]
Humidity Relative humidity below 95% RH (no dew formation)
Storage Temperature -20~65℃(-4~149°F)
Location No corrosive gas, flammable gas, oil mist and dust etc. indoors (Pollution degree 2 environment)
Altitude, Vibration Below 1,000m (From 1000 to 4000m, the rated input voltage and rated output current of the drive must be derated by 1% for every 100m.), below 9.8m/sec2 (1G)
Pressure 70~106kPa
Certificate/Compliance UL, CE

Catalog Download