Panasonic / Sunx FP-X0 Specifications

Excel Automation is an authorized Panasonic / Sunx distributor. Contact us with sales and application support.

Items Specifications
L14R L30R L40R L40MR L60R L60MR
Controllable I/O points Control unit DC input
8 points,
Relay
output
4 points,
Transistor
output
2 points
DC input
16 points,
Relay
output
10 points,
Transistor
output
4 points
DC input 24 points,
Relay output 12
points,
Transistor output 4
points
DC input 32 points,
Relay output 24
points,
Transistor output 4
points
When using FP-X E16
expansion I/O units
88 points max.
(3 expansion units
max.)
108 points max.
When using FP-X E30
expansion I/O units
130 points max.
(3 expansion units
max.)
150 points max.
(3 expansion units
max.)
When using FP0R
expansion units
196 points max.
(3 expansion units
max.)
216 points max.
(3 expansion units
max.)
Programming method/Control method Relay symbol/Cyclic operation
Program memory Built-in Flash-ROM (Free of backup battery)
Program capacity 2.5 k steps 8 k steps
No of
instruction
Basic commands Approx. 114 kinds
High-level commands Approx. 230 kinds
Processing speed 0.08 µs/step for basic
commands
0.32 µs for high-level
commands
(MV commands)
3 k steps: 0.08 µs/step for basic commands, 0.32 µs
for high-level commands(MV commands)
After 3 k steps: 0.58 µs/step for basic commands,
1.62 µs for high-level commands(MV
commands)
Basic time 0.15 ms
or less
0.18 ms
or less
0.31 to 0.35 ms
or less
0.34 to 0.39 ms
or less
I/O refreshing + basic time When using E16: 0.4 ms × No. of units
When using E30: 0.5 ms × No. of units
When using FP0 expansion adapters: 1.4 ms + the refreshing
time of the FP0 expansion unit
Memory for processing Relays External input (X) (Note 1) 960 points 1760 points
External output (Y) (Note 1) 960 points 1760 points
Internal relay (R) 1008 points 4096 points
Special internal relay (R) 224 points
Timer・Counter (T/C) 256 points (Note 2) 1024 points (Note 2)
Timer: (1 ms, 10 ms, 100 ms, 1 s)× 32767, Counter: 1 to 32767
Link relay (L) No 2048 points
Memory area Data register (DT) 2500 words 8192 words
Special data register (DT) 420 words
Link data register (LD) No 256 words
File registration (FL) No
Index register (I) 14 words (IO to ID)
Differential points Equivalent to program capacity
Master control relay (MCR) 32 points 256 points
Label number (JP+LOOP) 100 points 256 points
No. of step programs 128 (Engineering) 1000 (Engineering)
No. of subroutines 100 500
No. of interrupt programs Input: 8 programs, timing: 1 program
Sampling trace No Yes
Comments storage All of the I/O comments,explanations and block comments can
be saved.(Free of backup battery, 328 k bytes)
PLC link function No Yes
Constant scan In unit of 0.5 ms: 0.5 ms to 600 ms
Password Available (4 or 8 digits)
Upload protection Available
Self-diagnosis function Checks of the watchdog timer and the program syntax
Program editting during
Run
Available (Capacity modified simultaneously: 128 steps)
But comments cannot be modified during the process.
Available (Capacity modified simultaneously: 512 steps)
But comments can be modified during the process.
Downloading during Run Available
High-speed
counter
(Note 3,4)
Body input 1-phase, 4-channel
(20 kHz max.)
and 2-phase, 2-channel
(20 kHz max.)
1-phase, 4-channel (50 kHz max.)
and
2-phase, 2-channel (20 kHz max.)
Pulse output/
PWM output
(Note 3,4)
Body output Pulse:
1-channel
(20 kHz max.)
PWM:
1-channel
(1.6 kHz max.)
Pulse:
2-channel
(20 kHz max.)
PWM:
2-channel
(1.6 kHz max.)
Pulse: 2-channel (50 kHz)
PWM: 2-channel(3.0 kHz max.)
Pulse catch input/
Interrupt program
8 points
(High-speed counting and interrupt input included)
Periodical interrupt 0.5 ms unit: 0.5 ms to 1.5 sec., 10 ms unit: 10 ms to 30 sec.
Analog input No 2-channel (For inputting any of the
following items in each channel)
Potentiometer input
Min. resistance value of potentiometer:
5 kΩ
10-bit resolution (K0 to K1000)
Accuracy ± 1.0% F.S.+ accuracy of
external reistors
Thermistor input
For inputting the resistance value of the
thermistor
(Min. resistance value of external
thermistors + external resistance value
> 2 kΩ)
10-bit resolution (K0 to K1023)
Accuracy ± 1.0% F.S.+ accuracy of
external thermistors
Voltage input
Absolute max. input voltage: 10 V
10-bit resolution (K0 to K1023)
Accuracy ± 2.5% F.S.(F.S. = 10 V)
Calendar/clock No Yes
Flash ROM
backup
(Note 5)
Backup made
according to
commands of
F12 and P13
Data memory
(2500 words)
Data memory
(8192 words)
Automatic
backup when
power OFF
Counter: 6 points
(C250 to C255)
Process value of the
counter: 6 points
(EV250 to EV255)
Internal relays: 5 points
(WR58 to WR62)
Data memory: 300 words
(DT2200 to DT2499)
Counter: 16 points (C1008 to C1023)
Process value of the counter: 16 points
(EV1008 to EV1023)
Internal relays: 8 points
(WR248 to WR255)
Data memory: 302 words
(DT7890 to DT8191)
Backup battery No Yes (Backup lasting for the whole process)
RS485 communication port No Yes No Yes