Amerimation LSLV iS7

Eagle Sensors & Controls is an authorized Amerimation distributor. Contact us with application and sales support.

Key Features

  • Sensorless Vector & V/Hz control
  • Heat Sink Out the Back Mounting Option
  • Fieldbus and Closed Loop Options
  • HD operation: – 10 – 50°C
  • Powerful electric current type sensorless vector control

① Rated Motor

0008 0.75kW
0015 1.5kW
0022 2.2kW
0037 3.7kW
0055 5.5kW
0075 7.5kW
0110 11kW
0150 15kW
0185 18.5kW
0220 22kW
0300 30kW
0370 37kW
0450 45kW
0550 55kW
0750 75kW
0900 90kW
1100 110kW
1320 132kW
1600 160kW
1850 185kW
2200 220kW
2800 280kW
3150 315kW
3750 375kW

② Input Voltage

2 3-Phase 200~230[V]
4 3-Phase 380~480[V]

③ Keypad

N NON
S GLCD(Graphic Loader)

④ UL

O UL Type 1
E Enclosed UL Type 1
P Enclosed UL Type 12

 Filter

Blank NON
F EMC Filter

⑥ DC Reactor

Blank NON
D DC Reactor
R DB Resistor (Inner Mounted)

⑦ Customized Product

W Winder
S Synchronous
T Safety
V Marine

Specifications

Rated Input and Output: Input voltage of 200V class (0.75~22kW)
0008 0015 0022 0037 0055 0075 0110 0150 0185 0220
Applied Motor VT HP 2 3 5 7.5 10 15 20 25 30 40
kW 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30
CT HP 1 2 3 5 7.5 10 15 20 25 30
kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
Rated Output Rated Capacity (kVA) 1.9 3.0 4.5 6.1 9.1 12.2 17.5 22.9 28.2 33.5
Rated Current CT 5 8 12 16 24 32 46 60 74 88
VT 8 12 16 24 32 46 60 74 88 124
Output Frequency 0 ~ 400 [Hz]
Output Voltage (V) 3-phase 200 ~ 230V (Sensorless-1 : 0~300Hz, Sensorless-2, Vector : 0.1~120Hz)
Rated Input Available Voltage [V] 3-phase 200 ~ 230 VAC (-15% ~ +10%)
Frequency [Hz] 50 ~ 60 [Hz] (±5%)
Rated Current (A) CT 4.3 6.9 11.2 14.9 22.1 28.6 44.3 55.9 70.8 85.3
VT 6.8 10.6 14.9 21.3 28.6 41.2 54.7 69.7 82.9 116.1
2.1.2 Rated Input and Output: Input voltage of 200V class (30~75kw)
0300 0370 0450 0550 0760
Applied Motor VT HP 50 60 75 100 125
kW 37 45 55 75 90
CT HP 40 50 60 75 100
kW 30 37 45 55 75
Rated Output Rated Capacity (kVA) 46 57 69 84 116
Rated Current CT 116 146 180 220 288
VT 146 180 220 288 345
Output Frequency 0 ~ 400 [Hz]
Output Voltage (V) 3-phase 200 ~ 230V (Sensorless-1 : 0~300Hz, Sensorless-2, Vector : 0.1~120Hz)
Rated Input Available Voltage [V] 3-phase 200 ~ 230 VAC (-15% ~ +10%)
Frequency [Hz] 50 ~ 60 [Hz] (±5%)
Rated Current (A) CT 121 154 191 233 305
VT 152 190 231 302 362
Rated Input and Output: Input voltage of 400V class (0.75~22kW)
0008 0015 0022 0037 0055 0075 0110 0150 0185 0220
Applied Motor VT HP 2 3 5 7.5 10 15 20 25 30 40
kW 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 3.
CT HP 1 2 3 5 7.5 10 15 20 25 30
kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
Rated Output Rated Capacity (kVA) 1.9 3.0 4.5 6.1 9.1 12.2 18.3 22.9 29.7 34.3
Rated Current CT 2.5 4 6 8 12 16 24 30 39 45
VT 4 6 8 12 16 24 30 39 45 61
Output Frequency 0 ~ 400 [Hz]
Output Voltage (V) 3-phase 380 ~ 480V (Sensorless-1 : 0~300Hz, Sensorless-2, Vector : 0.1~120Hz)
Rated Input Available Voltage [V] 3-phase 380 ~ 480 VAC (-15% ~ +10%)
Frequency [Hz] 50 ~ 60 [Hz] (±5%)
Rated Current (A) CT 2.2 3.6 5.5 7.5 11.0 14.4 22.0 26.6 35.6 41.6
VT 3.7 5.7 7.7 11.1 14.7 21.9 26.4 35.5 41.1 55.7
Rated Input and Output: Input voltage of 400V class (0.75~22kW)
0300 0370 0450 0550 0750 0900 1100 1320 1600 1850 2200 2820 3150 3750
Applied Motor VT HP 50 60 75 100 125 150 200 250 300 350 400 500 600 700
kW 37 45 55 75 90 110 132 160 185 220 280 315 375 450
CT HP 40 50 60 75 100 125 150 200 250 300 350 400 500 600
kW 30 37 45 55 75 90 110 132 160 185 220 280 315 375
Rated Output Rated Capacity (kVA) 46 57 69 84 116 139 170 201 248 286 329 416 467 557
Rated Current CT 61 75 91 110 152 183 223 264 325 370 432 547 613 731
VT 75 91 110 152 183 223 264 325 370 432 547 613 731 877
Output Frequency 0 ~ 400 [Hz] (Sensorless-1: 0 ~ 300Hz, Sensorless-2, Vector: 0 ~ 120Hz)
Output Voltage (V) 3-phase 380 ~ 480V
Rated Input Available Voltage [V] 3-phase 380 ~ 480 VAC (-15% ~ +10%)
Frequency [Hz] 50 ~ 60 [Hz] (±5%)
Rated Current (A) CT 55.5 67.9 82.4 102.6 143.4 174.7 213.5 255.6 316.3 404 466 605 674 798
VT 67.5 81.7 101.8 143.6 173.4 212.9 254.2 315.3 359.3 463 590 673 796 948
Control
Control Method V/F control, V/F PG, slip compensation, sensorless vector-1, sensorless vector-2, vector control
Frequency Setting Resolution Digital command: 0.01Hz Analog command: 0.06Hz (maximum frequency: 60Hz)
Frequency Tolerance Digital command operation: 0.01% of the maximum frequency Analog command operation: 0.1% of the maximum frequency
V/F Pattern Linear, double reduction, user V/F
Overload Capacity CT current rating: 150% for 1 minute, VT current rating: 110% for 1 minute
Torque Boost Manual torque boost, automatic torque boost
Protective Functions
Trip Over voltage, low voltage, over current, over current detection, drive overheat, motor thermal protection, phase loss protection, overload protection, communication error, frequency command loss, hardware failure, cooling fan failure, pre-PID failure, no motor trip, external brake trip. Safety function, etc.
Alarm Stall prevention, overload, diminished load, encoder error, fan failure, keypad command loss, speed command loss.
Instantaneous Interruption Below CT class 15 msec (VT class 8 msec): operation continues (within rated input voltage, rated output) Over CT class 15 msec (VT class 8 msec): automatic restart
Environment
Cooling Type Forced air blast cooling: 0.75 ~ 15kW (200/400V class), 22kW (400V class) Inhalation cooling: 22 ~ 75kW (200V class), 30~375kW (400V class)
Protection Structure 0.75~22kW(200V), 0.75~75kW(400V): Open type IP 21(default), UL enclosed type 1(Option) 30 ~ 75kW(200V), 90~375kW(400V): Open type IP 00 (default), UL enclosed type 1 (Option) 0.75~22kW-2/4 and etc: Enclosed IP54 type, UL enclosed type 12
Surrounding Temperature CT (Heavy Duty) load: -10 ~ 50℃, (14 ~ 122℉) without ice or frost VT (Normal Duty) load: -10~ 40℃ (14 ~ 104℉) without ice or frost (It is recommended that you use less than 80% load when you use VT load at 50°C (122°F)) IP54 product: -10~40℃ (14~122℉) without ice or frost
Preservation Temperature -20 ~ 65℃ (-4 ~ 149℉)
Surrounding Humidity Below 95% RH of relative humidity (with no dew formation)
Altitude, Vibration Below 1,000m (From 1000 to 4000m, the rated input voltage and rated output current of the drive must be derated by 1% for every 100m.), below 5.9m/sec 2 (19.36 ft/sec 2, 0.6G)
Environment There should be no corrosive gas, flammable gas, oil mist or dust. Pollution Degree 2 Environment
Conformal Coating To meet the below IEC standard In the harsh operating environment and to enhance PCB Ass’y life cycle IEC 60721-3-3(3C2) / IEC 60068-2-43 / IEC 60068-2-60
Specifications
Operating Method Selectable among keypad/terminal block/communication operation
Frequency Setting Analog: 0 ~ 10[V], -10 ~ 10[V], 0 ~ 20[mA] Digital: keypad
Operating Function PID control, up-down operation, 3-wire operation, DC brake, frequency limit, frequency jump, second function, slip compensation, reverse rotation prevention, auto restart, drive by-pass, auto tune flying start, energy buffering, power braking, flux braking, leakage current reduction, MMC, easy start
Input Multi-function terminal (8 points)P1 ~ P81 NPN (Sink)/PNP (Source) selectable
Function: forward operation; reverse operation; reset; external trip; emergency stop; jog operation; sequential frequency-high; medium and low; multi-level acceleration and deceleration-high; medium and low; D.C. control during stop; selection of a second motor; frequency increase; frequency decrease; 3-wire operation; change to general operation during PID operation; main body operation during option operation; analog command frequency fixation; acceleration and deceleration stop selectable
Output Multi-function open collector terminal Drive fault output Below DC 46V 100mA
Multi-function relay terminal Below (N.O., N.C.) AC250V 1A, Below DC 30V 1A
Analog output 0 ~ 10 Vdc (below 20mA): selectable from frequency, current, voltage, direct current voltage
Certificate/Compliance UL, CE

Catalog Download